Sediment and biofilm affect disinfectant decay rates during long-term operation of simulated reclaimed water distribution systems

Abstract

Changing chemistry and microbiology of reclaimed water as it is conveyed via reclaimed water distribution systems (RWDSs) can influence water quality at the point of use. Two simulated RWDSs comprised of 0.32 cm tubes (“Tube” RWDSs) and 10 cm diameter pipes (“Pipe” RWDSs) were designed to investigate how extremes in water age (32 min versus 5 d) and surface area to volume ratio (6.25 cm−1versus 0.20 cm−1) affect the potential for sediment accumulation, disinfectant decay, and chemical and microbial water quality under controlled treatment conditions. Effluent from a conventional municipal wastewater treatment plant was breakpoint chlorinated and treated with and without biological filtration, followed by three disinfectant conditions: no residual, 4 mg L−1 chlorine or 4 mg L−1 chloramine. After three years of operation, accumulated sediment occupied 0.32–3.2% of the total volume of the first pipe segment. The unfiltered chlorine condition had an order of magnitude less influent turbidity and sediment accumulation than conditions with no residual or chloramine, resulting in lower levels of biological activity and slower depletion of disinfectants and dissolved oxygen. The sediment in pipes receiving chloraminated water was highly biologically active and created a high disinfectant demand due to nitrification. In contrast, the tube RWDSs did not accumulate sediment. The Tube rigs with chloramine and no residual had heavy bio-foulant growth, which resulted in rapid depletion of chloramine. Biofilm was the main source of disinfectant demand in the chlorine tubes. An improved holistic understanding of RWDSs chemistry, biology and operation will help achieve desired water qualities at the point of use.

Graphical abstract: Sediment and biofilm affect disinfectant decay rates during long-term operation of simulated reclaimed water distribution systems

Supplementary files

Article information

Article type
Paper
Submitted
01 Nov 2019
Accepted
01 Apr 2020
First published
03 Apr 2020

Environ. Sci.: Water Res. Technol., 2020,6, 1615-1626

Author version available

Sediment and biofilm affect disinfectant decay rates during long-term operation of simulated reclaimed water distribution systems

N. Zhu, K. Mapili, H. Majeed, A. Pruden and M. A. Edwards, Environ. Sci.: Water Res. Technol., 2020, 6, 1615 DOI: 10.1039/C9EW00978G

To request permission to reproduce material from this article, please go to the Copyright Clearance Center request page.

If you are an author contributing to an RSC publication, you do not need to request permission provided correct acknowledgement is given.

If you are the author of this article, you do not need to request permission to reproduce figures and diagrams provided correct acknowledgement is given. If you want to reproduce the whole article in a third-party publication (excluding your thesis/dissertation for which permission is not required) please go to the Copyright Clearance Center request page.

Read more about how to correctly acknowledge RSC content.

Social activity

Spotlight

Advertisements