Vladislav
Knytl
ab,
Pavel
Mašín
b,
Věra
Vlčková
d,
Jaroslav
Semerád
c,
Klára
Michalíková
c,
Petra
Najmanová
b and
Tomáš
Cajthaml
*ac
aInstitute for Environmental Studies, Faculty of Science, Charles University, Benátská 2, CZ-128 01, Prague 2, Czech Republic
bDekonta a.s, Dřetovice 109, CZ-273 42, Stehelčeves, Czech Republic
cInstitute of Microbiology of the Czech Academy of Sciences, Vídeňská 1083, CZ-142 00, Prague 4, Czech Republic. E-mail: cajthaml@biomed.cas.cz
dDepartment of Biotechnology UCT Prague, Technická 5, CZ-166 28, Prague 6, Czech Republic
First published on 13th October 2023
Pharmaceuticals and their metabolites are ubiquitous in the environment and represent typical anthropogenic micropollutants. Due to their low diffusive concentrations and often recalcitrant nature, the compounds are not completely removed by conventional biological wastewater treatment technologies, which emphasizes the need for tertiary treatment steps. This study was performed to evaluate the feasibility of photooxidation UV/H2O2 technology for the removal of selected pharmaceuticals (carbamazepine, diclofenac, hydrochlorothiazide, sulfamethoxazole, and tramadol) as a tertiary treatment step within the wastewater treatment plant (WWTP) process. The UV/H2O2 technology was compared with the more common treatment method of adsorption on granulated activated carbon (AC) in short-term and long-term tests. Both treatment systems were installed as pilot-scale units at a WWTP in a small village (equivalent of about 900 people) where a psychiatric hospital is located in the Czech Republic. The short-term tests highlighted several important aspects that need to be addressed within full-scale operations (e.g., mechanical pretreatment of wastewater, relation between H2O2 dose and UV dose). The initial concentration of tramadol was up to 5000 ng l−1, and that of carbamazepine and hydrochlorothiazide was up to 3000 ng l−1 in the WWTP outflow. The results showed that both units were capable of removing more than 95% of the pharmaceuticals during the long-term tests. As oxidation processes can generate transformation products (TPs), the ecotoxicity evaluation was addressed. Ecotoxicity using the bioluminescence bacterium Vibrio fischeri and the rainbow trout gill cell line (RTgill-W1) did not indicate any increase in ecotoxicity parameters in comparison to the inflow water samples for both units. Both processes were finally evaluated from an economical point of view, and the pilot-scale AC unit was more favorable in this context; however, estimations for a full-scale system suggest that the UV/H2O2 system is more economically feasible in terms of operational costs.
Water impactMicropollutants, including pharmaceuticals and their metabolites, often persist in effluent discharged from wastewater treatment plants. Here, two pilot-scale tertiary treatment approaches—UV/H2O2 photooxidation and adsorption on granulated activated carbon—were compared for their efficiency to degrade selected pharmaceuticals. Both units removed >95% of pharmaceuticals from real wastewater. The methods were also evaluated in terms of cost-effectiveness for full-scale application. |
Pharmaceuticals and their metabolites are ubiquitous in the environment.3 Their occurrence in wastewater has been confirmed in many countries around the world.4–6 Despite a significant reduction in concentrations, the majority of current wastewater treatment plants (WWTPs) are unable to completely eliminate pharmaceuticals from treated water. Some of the most persistent compounds can be detected even in groundwater hundreds of meters from the place of infiltration.7
To improve the removal of micropollutants, various technologies have been investigated in recent years as a possible final treatment step.8,9 Despite the vast number of laboratory-scale studies, only a few pilot- and full-scale studies are available regarding this problem.8 Most advanced legislative regulations came into effect in Switzerland, requiring approximately 100 municipal wastewater treatment plants in the country to be upgraded within the next 20 years to remove micropollutants from the final effluent.10
Advanced oxidation processes (AOPs) have been shown to be promising methods for the removal of various organic micropollutants from drinking water and wastewater. AOPs can be categorized according to the mechanism of oxidation into ozone-based, UV-based, electrochemical, catalytic, and physical AOPs.11 Recently, the combination of AOP implementations has been favored in the literature as an efficient solution in addressing the issue of global environmental waste management.12
Among those UV-based AOPs, UV-oxidation with hydrogen peroxide (H2O2), usually referred to as UV/H2O2, has attracted great attention, and numerous advantages have been documented for micropollutant control. Although simple UV light application does not yield satisfactory results, amendment of oxidizing agents (H2O2, S2O82−) together with the UV light potential for generating radicals has shown significant improvements.13,14
One of the major concerns regarding AOP-based technologies for water purification is that most organic pollutants are not completely mineralized but are partially oxidized into transformation products (TPs), adding chemical composition complexity to the treated water and posing risks to humans, ecological systems, and the environment.15 One parent compound can be oxidized into several TPs.16 Analytical identification of the whole spectrum of possible TPs is often beyond analytical capabilities. Up to hundreds of new TP chemical formulas with an increased degree of oxidation and decreased aromaticity were obtained by using ultrahigh-resolution mass spectrometry after drinking water treatment by the UV/H2O2 process.17 Several toxicological parameters were used as markers of possible higher toxicity of TPs. Vom Eyser et al. (2013) detected several TPs in ozonation and UV/H2O2 treatment processes.18 Accompanying analysis showed no genotoxic, cytotoxic or estrogenic potential for the investigated compounds after oxidative treatment of real wastewaters. Another finding was published by Han et al. (2018), who documented increased cytotoxicity and chromosome damage effects caused by TPs generated during ozonation.19 The fate of the generated TPs, their accumulation and chronic toxicity are under continual research.
According to available review articles, UV/H2O2 was confirmed as a suitable solution for the removal of various pharmaceuticals, but mostly at the laboratory scale.11 Although there have been a few documented attempts, studies employing UV/H2O2 as a final clean-up step (tertiary degree) within the WWTP process are scarce. Baresel et al. (2019) used UV/H2O2 for the removal of pharmaceutical residues from municipal wastewater, documenting satisfactory removal efficiencies for pharmaceuticals detected in the effluent of Stockholm's largest WWTP.20 Earlier, another attempt was well documented by Martijn et al. (2007), who implemented the UV/H2O2 process within a drinking water treatment plant.21 Sarathy et al. (2011) tested oxidation processes on natural organic matter when using a pilot-scale UV/H2O2 unit.22 Lhotský et al. (2017) successfully used UV/H2O2 for groundwater treatment containing a commingled plume of pharmaceuticals and aromatic compounds.23 Nevertheless, it is always necessary to compare novel treatment approaches with more commonly available technologies, such as adsorption on active carbon, or to consider their possible combination, which can increase their efficiency and usability.
In this study, we focused on the field evaluation of UV/H2O2 and its comparison to a more commonly used technology – adsorption on active carbon (AC) particles. Both pilot-scale units were designed as final (tertiary) treatment steps at a WWTP for the removal of pharmaceuticals from wastewater. As mentioned before, the lack of pilot-scale or full-scale studies on sites treating real wastewater limits the evaluation of UV/H2O2 technology for tertiary treatment within the WWTP process. Furthermore, the comparison of both technologies in the current study was performed on a site representing a village with a psychiatric hospital (see below). The efficiency was monitored using appropriate analytical methods, ecotoxicology tests and other parameters that can be used as surrogates in practice. Finally, both units were economically evaluated in terms of operating costs.
Fig. 1 A) A general scheme of the pilot unit setup including both AC and UV/H2O2 units and B) a more detailed scheme of the UV/H2O2 pilot unit. |
UV Dose = I × t | (1) |
I = average irradiance
t = time of exposure
The average UV irradiance in the empty reactor was measured by a portable radiometer equipped with a UVC probe. The average value inside the quartz glass cylinder was 2500 μW cm−2. Three flow rates were tested, specifically, 4, 8 and 16 L min−1, and the average UV dose for each flow rate according to the abovementioned equation was 1750, 3500, and 7000 J m−2, respectively. The last flow rate (16 l min−1) represented the upper limit for feasible operation of the unit regarding the mechanical pretreatment of the wastewater.
The calculated UV doses do not represent the actual values due to the turbidity of the real wastewater and the presence of H2O2 in the treated water, which can significantly influence ultraviolet transmission (UVT). To achieve more precise values, the (real/active) UV doses were calculated using the following simplified equations:25
UV dose for the perfect collimated beam:
(2) |
(3) |
D = UV dose (mJ cm−2)
E e = UV irradiance entering the water
F i = the fraction of UV with path length di
P f = the Petri factor
P e = the total radiant power entering the water spread over area A
R = reflectance at the air–water interface
d = path length (cm); d1, dn = multiple path lengths in a non-uniform reactor
a 254 = UV absorption coefficient (cm−1) at 254 nm
t = exposure time(s)
Q = flow rate
The UV absorption coefficient was determined in a water sample collected from the sampling port before the mechanical pretreatment step. Based on calculations according to eqn (3), the operating effective UV doses for 4, 8 and 16 l min−1 were determined to be 930, 465 and 233 J m−2, respectively. It is noteworthy that these calculations are simplifications and do not account for hydraulic efficiency parameters.25 The effect of H2O2 concentration on the absorption coefficient was assessed by spectrophotometric measurements (see section 2.6.3). The differences between average UV doses (eqn (1)) and real/active UV doses (eqn (3)) document that the geometry of the reactor, water parameters and especially its turbidity play crucial roles in UV/H2O2 efficiency. The rising complexity of the wastewater matrix can negatively affect the UV fluence in the photoreactor and the treatment efficiency.26
The treated water flowing from the UV/H2O2 unit contained a residual concentration of H2O2. To remove this residue, an open AC trap was installed at the unit outflow. The function of this granular AC bed (20 kg) was either to catalyze H2O2 decomposition27 or to remove possible oxidation by-products or degradation products of pharmaceuticals.
Chemical structure | |||||
---|---|---|---|---|---|
Compound | Carbamazepine | Diclofenac | Hydrochlorothiazide | Sulfamethoxazole | Tramadol |
Usage | Anticonvulsant, antiepileptic | Anti-inflammatory | Diuretic medication | Antibiotic | Opioid pain medication |
Formula | C15H12N2O | C14H11Cl2NO2 | C7H8ClN3O4S2 | C10H11N3O3S | C16H25NO2 |
CAS number | 298-46-4 | 15307-86-5 | 58-93-5 | 723-46-6 | 27203-92-5 |
MW (g mol−1) | 236.269 | 296.148 | 297.74 | 253.279 | 263.381 |
logKow | 2.5 | 0.7 | 0.89 | 3.01 |
The samples were collected at the outflow of the AC and UV/H2O2 units (sampling ports in Fig. 1). The samples were filtered using a glass filter (0.45 μm) and extracted using solid-phase extraction (SPE) using SPE columns (LiChrolut® EN, Merck KGaA). The columns were conditioned with 3 ml of methanol and then 3 mL of deionized water. The columns were loaded with 500 ml of a water sample. Afterward, the SPE columns were dried to remove the remaining water. The sample extracts were eluted with 3 ml of acetonitrile/methanol (50/50) and evaporated under a stream of nitrogen. The samples were redissolved in 1 ml acetonitrile and analyzed using HPLC-MS/MS (Accela 1250) equipped with PAL Accela Open AS and TSQ Quantum Access Max (Thermo Scientific, USA). For the separation, the column Luna Omega 1.6 μm polar C18, 50 × 2.1 mm was used equipped with precolumn C18, 2.1 mm (Phenomenex, USA). The gradient elution method was used, using A – water + 0.1 v/v% HCOOH and B – methanol + 0.1 v/v% HCOOH. The gradient program was as follows: 0 min, 20% B; 0.5 min to 2 min, a linear gradient to 95% B; and 2 min to 5 min, 95% B was maintained.
A TOC analyzer (Liqiu TOC II, Elementar, Germany) was employed using catalytic combustion with infrared spectrophotometry detection. For determination of the UVA254 parameter, the collected water samples were filtered with a 0.45 μm membrane filter and analyzed using a Shimadzu UV 1800 UV/VIS spectrophotometer (Japan) onsite. Attention was given to the immediate processing of the samples due to the influence of residual H2O2 on organic compounds. The residual H2O2 concentration was determined by a titration method using potassium iodide in the presence of the catalyst [(NH4)6Mo7O24·4H2O].32
Pharmaceutical (ng L−1) | Inflow to WWTP | Outflow from WWTP | Activated sludge in outflow (ng g−1) | |||
---|---|---|---|---|---|---|
Average | RSD [%] | Average | RSD [%] | Average | RSD [%] | |
Tramadol | 2102.9 | 7.4 | 2234.5 | 3.3 | 122.8 | 8.9 |
Carbamazepine | 2453.6 | 2.8 | 2526.2 | 5.7 | 135.1 | 4.7 |
Sulfamethoxazole | 111.0 | 1.4 | 819.6 | 6.6 | 30.9 | 7.6 |
Hydrochlorothiazide | 3135.0 | 7.9 | 2837.3 | 8.9 | 121.5 | 4.6 |
Diclofenac | 2233.7 | 7.7 | 1368.6 | 6.2 | 77.2 | 2.2 |
The results in Table 2 show that the common treatment process within the WWTP is not sufficient to efficiently remove any of these compounds. Moreover, the concentrations of some of the compounds (carbamazepine, tramadol) were not affected at all. Traces of these pharmaceuticals were also detected in groundwater samples extracted from historic wells downstream from the WWTP.24 These findings are in agreement with the literature when carbamazepine is well documented for its persistence caused by generally low biodegradability.33,34
The treated water from the WWTP contained a large amount of activated sludge particles. The analytical results of the pharmaceuticals in the particles are also summarized in Table 2. All the pharmaceuticals were detected at concentrations up to hundreds of ng g−1. Removal of these particles is desirable not only to increase the efficiency of the treatment process but also to prevent their accumulation in the recipient sediments, where they can represent a secondary pollution risk.
The additional parameters pH, TOC, UVA254, COD (Cr) (chemical oxygen demand) and BOD (biochemical oxygen demand) of the wastewater from the outflow are summarized in Table 3.
Units | Wastewater inflow parameters | Wastewater outflow parameters | |||
---|---|---|---|---|---|
Average | RSD [%] | Average | RSD [%] | ||
TOC | mg l−1 | 202.4 | 24.7 | 10.1 | 8.4 |
UVA254 nm | cm−1 | 2.8 | 9.6 | 0.2 | 5 |
COD (Cr) | mg l−1 | 500.8 | 19.4 | 40.8 | 10.4 |
BOD | mg l−1 | 422.8 | 17.3 | 2.6 | 7.9 |
pH | 7.1 | 13.1 | 7.7 | 8.1 |
The pH value of wastewater flowing into the experimental setup was between 7 and 8 during the whole test. The TOC parameter was 10.1 mg l−1, and this value was also stable during the experiment. The BOD/COD ratio was under the value of 0.1, which documents advanced previous biodegradation in the treated water due to the WWTP treatment processes.
The data in Fig. 2 show similar TOC concentrations in all the UV/H2O2 variants of the short-term test. The explanation lies in only partial decomposition of macromolecular organic compounds.35,36 The data document that the TOC parameter is not suitable for monitoring the removal efficiency of micropollutants in real wastewater via the UV/H2O2 treatment process. The AC unit caused a reduction in the TOC concentration of more than 50% to 4.3 mg l−1.
The UVA254 parameter representing the absorption of UV light at 254 nm is also proportional to the content of organic matter in water with respect to the presence of an aromatic moiety. Contrary to TOC, the parameter UVA254 showed a decrease in comparison to the inflow values (Fig. 2). The reduction in UVA254 indicates a loss of aromatic and conjugated double bond structures of the effluent organic matter (EfOM).35 Such partial oxidation typically leads to the opening of phenolic rings and the degradation of organic compounds in the treated water.37 Residual H2O2 also has an influence on the absorbance of the samples. The final UVA254 value without residual H2O2 was obtained by subtracting the molar absorption coefficient of the residual H2O2 from the recorded value. The variant with the highest UV dose and the highest dose of 35% H2O2 (0.5 ml min−1 – 7000 J m−2) showed a 24% decrease in UVA254 after subtracting the residual H2O2 absorbance.
Concentrations of the pharmaceuticals in the wastewater treated by each of the tested UV/H2O2 variants and adsorption on AC are summarized in Fig. 3.
The highest removal efficiency was found with the highest UV dose (85–93% removal efficiencies). Higher efficiencies were generally observed with increasing H2O2 dose for the same UV dose level. This corresponds to the highest decrease in the UVA254 parameter (Fig. 2). No preferential oxidation of the individual pharmaceuticals in the wastewater (tramadol, carbamazepine, hydrochlorothiazide, and diclofenac) was observed. Although sulfamethoxazole was reported in previous studies at this site7,24 as well as during the long-term test in this study (see below), its concentrations reached only a maximum of tens of ng l−1 during the short-term test. The AC unit reached up to 99% removal efficiency. As discussed above, the regulation of the flow rate through the system, while maintaining the constant H2O2 dose pump, had an effect on the concentration of H2O2 in the treated water. The initial H2O2 concentrations in all the variants and UV dose effects on the removal of the pharmaceuticals are shown in Fig. 4A.
The trends of the curves (black line) show proportionality between the removal efficiency of pharmaceuticals and the increasing UV dose and concentration of H2O2 (Fig. 4A). For instance, the curve representing 7000 J m−2 clearly shows a decreasing proportional trend depending on the rising concentration of H2O2 (only an 8% rise between variants for 40 mg l−1 and 120 mg l−1 H2O2). Higher concentrations of H2O2 produce increasing recombination of OH radicals and therefore substantially decrease the removal of pharmaceuticals. A similar finding was observed by Somathilake et al. (2018) under laboratory conditions38 and was confirmed in a real pilot wastewater treatment.20 Lower UV doses showed a more considerable increase in the removal efficiency with respect to increasing concentrations of H2O2. Nevertheless, the overall removal efficiency was lower (max. 32% for 1750 J m−2 and max. 67% for 3500 J m−2). The discrepancy (10 and 15 mg l−1 of H2O2) in the case of the lowest UV dose was caused by a temporary accidental decrease in the efficiency of the mechanical water pretreatment, which was observed during testing of this UV dose.
The decrease in UVA254 after subtracting the residual H2O2 absorbance (gray line) is also depicted in the graph (Fig. 4A). Similarly, the decrease was dependent on the UV dose and the H2O2 concentration. The maximum decrease (24%) was observed for the variant with the highest UV dose (7000 J m−2) and H2O2 concentration. For better visualization (Fig. 4B), the correlations between the ratio of the removal efficiency and UVA254 (Y axis) with increasing doses of H2O2 (X axis) were depicted. The variants with UV doses of 7000 and 3500 J m−2 showed similar horizontal curves with correlation coefficients (R2) of 0.87 and 0.90, respectively. The combination with the UV dose 1750 J m−2 is not shown due to the low removal results and a temporary accidental decrease in the efficiency of the mechanical water pretreatment.
The flow rate was set to 5 l min−1 throughout the whole test, and the theoretical UV dose was then 5600 J m−2. Between Apr 25 and May 22, the dose of H2O2 was set to 50 mg l−1. The removal efficiency for UV/H2O2 was above 95% for both sampling events. The sample from May 3 was also analyzed without any addition of H2O2 (labeled as UV). The results confirmed that only UV photolysis (254 nm) without any other amendments is not sufficient to achieve satisfactory results regarding pharmaceutical removal. Similar results were shown, for example, by Chowdhury et al. (2020).39
It was observed that the AC trap capacity was not sufficient to remove the residual H2O2. For this reason, the H2O2 dose was lowered to 30 mg l−1. The results from May 22 to 29 still showed very good removal efficiency over 95%. Interestingly, for UV/H2O2, the removal efficiency was even higher in comparison to short-term testing (Fig. 4A – 40 mg l−1 H2O2 and theoretical UV dose 7000 J m−2). The explanation lies in the installation of new sand filters with higher capacity and therefore more efficient pretreatment of the wastewater. The removal efficiency dropped to 84% on June 5 due to an accidental inflow of water with higher turbidity from the WWTP. The pretreatment system was not capable of sufficient removal of the activated sludge particles.
The concentrations of the pharmaceuticals in the samples from the AC unit were below the respective detection limits throughout the whole long-term test, documenting that there were no breakthroughs due to insufficient AC adsorption capacity. The long-term operation of the AC unit was prolonged to monitor the breakthrough capacity of the AC bed. The flow rate was alleviated to 12 l min−1. Samples of water flowing from the AC unit were collected every 14 days. The breakthrough was noted in November 2020 as the removal of the pharmaceuticals dropped to 75%. All previous samples showed over 95% removal efficiency. The total amount of water flowing through the AC unit was approximately 2000 m3, this amount also represented the breakthrough limit for the AC unit. It is important to note that this value was influenced by time periods where the pretreatment system was not functioning properly. Otherwise, the breakthrough limit of AC columns could have been higher.
Parameter | UV/H2O2 | AC adsorption |
---|---|---|
Pretreatment | - Mechanical pretreatment system | - Mechanical pretreatment system |
Energy consumption | - Pumps for water flow | - Pumps for water flow |
- UVC light lamps | ||
- H2O2 dosing pump | ||
Agents | - H2O2 solution (needed periodical replenishment) | - AC particles – including regeneration of AC or not |
- AC particles for AC carbon trap | ||
Additional materials | - UVC light lamps change (1× per year) | |
Maintenance | - Pretreatment system | - Pretreatment system |
- UV dose measurements | - AC tanks maintenance | |
- H2O2 dosing | ||
- Cleaning quartz glass |
The data show that the costs for the treatment of 1 m3 wastewater based on the mentioned parameters are 0.95 € per m3 for the AC unit and 1.15 € per m3 for the UV/H2O2 unit. These values are substantially higher in comparison to available estimations for UV/H2O2 between 0.08 and 0.13 € per m3 by Karl and Dolling (2018)42 or even <0.08 € per m3 by Baresel et al. (2019).20 These estimations are for full-scale application to much larger WWTPs with wastewater flow rates over 1000 m3 h−1. Estimations based on this study are 0 and 3 m3 h−1 pilot tests. It can be assumed that with a larger scale, the price per m3 will be significantly lower.
It is important to note that full-scale operation on the site might be different. The annual flow rate through this WWTP is 120000 m3 (approximately 13 m3 h−1), which means the consumption of 24 t of granulated AC. In fact, the AC amount could be lower with a more robust pretreatment system, which could increase the estimated breakthrough limit. If the full-scale operation included regeneration of granulated AC, it can be generally assumed that the environmental impact (in the sense of life cycle assessment) and even economical parameters of the full-scale process could be more favorable. At the same time, it is noteworthy that the possibility of AC regeneration in Central Europe is still scarce. Generally, the consumption of AC in the case of full-scale treatment might cause the UV/H2O2 technology to be more favorable, especially in the case of decreasing costs of UV/H2O2 due to more efficient reactor setups with protected UVC lamps inside the reactors, and therefore better utilization of UVC light.25 On the other hand, a construction of the full-scale UV/H2O2 unit will be more expensive in comparison to the AC technology. Finally, the removal of residual H2O2 by an AC trap installed at the outflow from a UV/H2O2 full-scale technology should be more robust to achieve sufficient removal of residual H2O2.
The removal efficiency of the monitored pharmaceuticals is dependent mainly on the concentration of H2O2 in treated water and the UV dose. It was found that high concentrations of H2O2 together with high UV doses can inhibit the removal of pharmaceuticals, probably due to OH− recombination processes. Furthermore, the production of residual concentrations of H2O2 in wastewater could represent a problem within continuous and large-scale operation, as releasing the oxidizing agent to a recipient is undesired. To monitor the treatment efficiency, UVA254 was selected as a reliable surrogate parameter. Higher UV doses (3500 and 7000 J m−2) showed a good correlation between UVA254 and the removal efficiency of the pharmaceuticals. The TOC parameter was not sensitive enough for real wastewater containing a rich spectrum of various organic compounds. Adsorption on AC particles showed over 95% removal efficiency even in the prolonged period (up to 2000 m3).
The toxicity of the treated wastewater regarding possible incomplete oxidation and generation of intermediate products was evaluated by an acute toxicity test using Vibrio fischeri and cytotoxicity toward RT-gill-w1 cells. It was confirmed that the samples taken from UV/H2O2 did not show any increase in the ecotoxicity parameters in comparison to the inflow water samples.
Both technologies were proven within this pilot study to be suitable for tertiary wastewater treatment with respect to the removal of pharmaceuticals. The importance for proper setting of the operation parameters is crucial and should be evaluated before using each technology. Economical evaluation of both systems during long-term operations showed better results for the AC carbon unit. This might change if we took into account full-scale application for the whole WWTP (120000 m3 per year).
The authors emphasize the need for more pilot-scale and full-scale studies to evaluate the efficiency and economic feasibility for comparison with other technologies e.g., adsorption on active carbon, ozonation, etc.
Footnote |
† Electronic supplementary information (ESI) available. See DOI: https://doi.org/10.1039/d3ew00258f |
This journal is © The Royal Society of Chemistry 2024 |