Theresa
Pistochini
ab,
Graham
Jaeger
bc,
Christopher D.
Cappa
a and
Richard L.
Corsi
*a
aDepartment of Civil and Environmental Engineering, University of California Davis, 1 Shields Avenue, Davis, CA, USA. E-mail: rlcorsi@ucdavis.edu
bWestern Cooling Efficiency Center, University of California Davis, 215 Sage Street, Suite 100, Davis, CA, USA
cDepartment of Mechanical and Aeronautical Engineering, University of California Davis, 1 Shields Avenue, Davis, CA, USA
First published on 25th October 2024
Filtration performance of do-it-yourself (DIY) box fan filters deployed across a university campus was assessed over an academic year. Four DIY air filters were constructed from box fans and air filters with a minimum efficiency reporting value (MERV) of 13 and deployed in four spaces (two laboratories that include sources of particles and two offices). They were operated 9 hours daily with a programmable timer and were continuously monitored with power meters. Particle concentrations in the spaces were continuously monitored with low-cost nephelometers. The particle size dependent clean air delivery rate (CADR) and single pass filtration efficiency for each box was measured in a laboratory before deployment and every 10 weeks, for a total of five measurements over 40 weeks. We find that these DIY box fan filters maintain robust performance over time, with each air filter maintaining at least 60% of its initial CADR at the end of the 40 week study even with daily operation in environments with modest particle concentrations. CADR values for particles of 1.0–3.0 μm optical diameter averaged 34% higher than CADR values for 0.35–1.0 μm particles, aligning with MERV 13 filter size-dependent filtration expectations. Reductions in CADR over time were attributed to a reduction in filtration efficiency, likely due to a loss of filter electrostatic charge over time. There was no strong indication that increased resistance due to particle accumulation on filters appreciably decreased flow rates over time for any of the fans. The long-term robustness of DIY box fan air filters demonstrates their validity as a cost-effective, high performance, alternative to portable high efficiency particulate air (HEPA) filters.
Environmental significanceThe work provides insight into the ability of low-cost do-it-yourself (DIY) air filters to improve the indoor environment by reducing particle concentrations and related human exposure. The longterm and size-dependent performance is studied to enable analysis of how DIY air filters will perform with regards to particles generated by different sources (e.g. wildfire smoke vs. respiratory aerosols) |
Portable filtration has been observed to reduce the concentration of respiratory aerosols and the risk of respiratory infection transmission between occupants in a variety of building types. In a field study in 16 homes with an individual positive for COVID-19, Myers et al. observed a reduction in SARS-CoV-2 RNA positive air samples in the room most often occupied by the infected individual when a portable HEPA filter was operated.5 In a field study of a hospital patient room and adjacent corridor and nurses' station, Buising et al. demonstrated that a surrogate for respiratory aerosol rapidly travelled from the patient room to adjacent spaces and that portable HEPA filters increased aerosol removal rates and decreased spread outside the patient room.6 In a field study in a secondary school with 90 students, Banholzer et al. found that air samples positive for SARS-CoV-2 were reduced from 8% to 5% when a portable HEPA filter was operated in classrooms.7 Additionally, average viral concentrations of positive air samples were substantially reduced by operation of the HEPA filter. Although the infection transmission risk odds ratio for SARS-CoV-2 was calculated to be comparable for the periods with and without portable air filters, the short two-week intervention and low number of infections resulted in high uncertainty in this conclusion. In a six-month study comparing two daycare centres with a portable HEPA filter intervention to a large reference population, Vartiainen et al. demonstrated that absenteeism due to child illness was reduced by 32% in the daycare centres with HEPA filters.8 These field results are consistent with infection transmission risk modelling that predicts a reduced number of infections when using air filters that remove respiratory aerosols from the indoor air.8,9
Filtration has additional health benefits in reducing occupant exposure to particles including pollen, pet dander, indoor cooking generated particle pollution, and outdoor-source particle pollution (e.g. vehicle exhaust, forest fire and residential wood smoke). A general review of the health benefits of particle filtration by Fisk in 2013 concluded that the majority of well-designed intervention studies employing particle filtration report modest statistically significant improvements in health, particularly for people with allergies or asthma. Notably, two of the studies reviewed demonstrated portable HEPA filtration used in homes reduced both particulate matter exposure and health markers (vascular and endothelial function) that are predictors of future coronary events.10,11 A 2021 review of 21 papers related to portable air cleaners and published between 2005 and 2020 by Cheek et al. showed substantial reductions (22 to 90%) of indoor particulate matter less than 2.5 microns (PM2.5) when portable air filters were in use.1 Health benefits of reduced particulate matter exposure assessed by these studies were also summarized, but evidence of benefits was limited and inconsistent. However, the authors note that the cumulative body of scientific evidence supports that there are positive health benefits associated with reduced PM2.5 exposure.
A limitation of the widespread deployment of portable HEPA filters is cost. In a cost-benefit analysis of HEPA filtration in 2017, Fisk and Chan estimated the cost of procuring HEPA filtration for a home at $0.55 to $1.40 per m3 h−1 of clean air delivered (CADR) and determined that the mortality-related economic benefits exceed the cost of purchasing and operating air cleaners when used over their multi-year life.12 In 2022, Dal Porto et al. estimated the cost of HEPA filtration at $0.44 to $0.51 per m3 h−1 of CADR.3 The American Home Appliance Manufacturers (AHAM) recommend a CADR target of 12 m3 h−1 per m2 of floor area, which equates to $5.39 to $6.25 per m2 of floor area when applying costs from Dal Porto et al.13 Therefore, HEPA filtration may not be a priority or may be too costly for some residents and operators of commercial buildings (e.g. schools, daycares, offices). The CR box offers a first-cost that is an order of magnitude below HEPA at $0.05 to $0.07 per m3 h−1 of CADR.3 While multiple papers have been published documenting the filtration performance of new CR boxes,3,14–18 there is no published data on the longevity of the devices and their long-term performance. The purpose of this research was to assess the filtration performance of CR boxes operated daily over a 9 month academic year to determine how well these low-cost do-it-yourself filters perform over time.
CR box | Space | Building ventilation type | Ventilation schedule |
---|---|---|---|
1 | Bainer – lab | 100% OA | All hours |
2 | WCEC – lab | Local exhaust | Varies (manual) |
3 | Kemper – office | 100% OA | All hours |
4 | Ghausi – office | Recirculated | M–F 6:00–18:00 |
Measurements were conducted in a conference room at WCEC with measured volume of 120 m3 (Fig. 1). The mechanical heating, cooling, ventilation and filtration system for the conference room was shut off so that the only particle loss mechanisms in the room were deposition, air exchange through infiltration, and removal by the CR box. The total particle loss rate for combined deposition and infiltration was measured without the CR box operating. This loss rate was subtracted from the particle loss rate calculated with the CR box operating to obtain the particle loss rate attributable to the CR box.
The following procedure was used to collect the data required to calculate the CADR:
1. Salt particles were generated for 10 minutes while the CR box was off. Two fans placed on the table mixed the room air at low speed during this period.
2. The mixing fans were turned off. The room was left undisturbed for 10 minutes.
3. The CR box was turned on for 30 minutes to measure the exponential decay of the particles.
In the first round of testing, particle concentrations by size bin were measured every 5 seconds with two types of instruments, a laboratory-grade aerodynamic particle sizer (APS; TSI model 3321) and two low-cost optical particle counters (OPC; Alphasense OPC-N3 packaged into QuantAQ-MODULAIR-PM). This was done to correlate the particle concentration measurements for the lower-accuracy OPCs, which were available for the duration of the yearlong study, with the higher accuracy APS, which was only available intermittently. Kaur and Kelly evaluated nine Alphasense OPC-N3 sensors and reported a negative bias for particle concentration relative to the APS, as well as substantial inter-sensor variability.19 Since CADR is calculated based on the change in particle concentration over time, an error in absolute sensor accuracy (i.e. gain) does not impact the results. However, sensor non-linearity does impact the results and is important to correct for.
As described in the ESI,† the particle aerodynamic diameters defining each APS bin were converted to physical diameter (assuming spherical particles) to account for particle density and aligned with the optical diameter bins for the OPC. A set of empirical correlations were then developed to convert OPC particle concentrations to APS-equivalent particle concentrations. The APS-equivalent values were then used to calculate the air changes per hour (ACH) for particle removal (bins 0–6) as described by Dal Porto et al. for the CR box including filtration (f), deposition (d), and infiltration (i), termed ACHf+d+i.3 Particle removal by deposition may be enhanced by the increased turbulence engendered by the fan on the CR box, enhancing the apparent losses due to filtration alone. We distinguish below between depositional losses with (d + fan) and without (d) the CR box fan.
Curve fits were calculated with Igor Pro v9.02 using the Levenberg–Marquardt least-squares method. The 95% confidence interval for each fit coefficient for ACHf+d+i is also reported.
The air changes per hour (ACH) for deposition (d) and infiltration (i), termed ACHd+i, was measured in an experiment in the conference room where:
1. Salt particles were generated for 10 minutes. Two fans placed on the table mixed the room air at low speed during this period.
2. The mixing fans were turned off. The room was left undisturbed for 24 hours.
The APS-equivalent values were then used to calculate for particle removal as described by Dal Porto et al.3 Particle concentrations for larger particle diameters dropped below the detection limit of the OPC before the end of the 24 hour settling period. The particle loss rate analysis was limited to the period where the particle concentration was above 0. The particle loss rate for deposition and infiltration and analysis period for each bin are shown in Table 2. As generally expected, ACHd+i increased with particle size.
Bin (j) | APS physical diameter (μm) | OPC optical diameter (μm) | ACHi+d (h−1) | Analysis period (h) |
---|---|---|---|---|
0 | ≤0.46 | 0.35–0.46 | 0.141 | 24.0 |
1 | 0.46–0.66 | 0.46–0.66 | 0.166 | 24.0 |
2 | 0.66–1.03 | 0.66–1.0 | 0.202 | 21.7 |
3 | 1.03–1.28 | 1.0–1.3 | 0.245 | 14.7 |
4 | 1.28–1.72 | 1.3–1.7 | 0.284 | 12.0 |
5 | 1.72–2.30 | 1.7–2.3 | 0.378 | 6.5 |
6 | 2.30–3.07 | 2.3–3.0 | 0.523 | 1.9 |
The CADR for the air cleaner for each particle size bin “j” was then calculated from eqn (1):
CADR(j) = (ACHf+d+i(j) − ACHd+i(j))V | (1) |
To simplify the presentation of the data, the CADR results from bins 0 to 6 were averaged into two groups: particles with optical diameter less than 1 μm (more representative of particle diameters observed in wildfire smoke) and particles with optical diameters between 1 to 3 μm (more representative of particle diameters observed in infectious respiratory aerosols).20,21 The average CADR for all bins was also calculated. All averaging calculations weighted the CADR measurement for each bin equally. To estimate the uncertainty of the CADR measurement method, we measured the CADR of box 3 on speed high 10 times. This testing was performed after the 40 week deployment. The repeat measurements included setup and takedown of the CR box and the instrumentation to account for minor differences in placement. The uncertainty (two standard deviations) was 6% of the average measurement for 0.35 to 1 μm optical diameter particles and 5% for 1 to 3 optical diameter particles. This uncertainty (as a percentage) was applied to all CADR measurements.
(2) |
While the SPFE and pressure drop data were collected every 10 weeks, the sensor access door was unintentionally not taped during SPFE testing that occurred on weeks 10 and 20. Leaks in the bottom of the box made the results unreliable and therefore only SPFE results from 0, 30, and 40 weeks are presented. The access door was securely taped for the CADR testing and those results were unaffected.
Bin (j) | OPC optical diameter (μm) | Low speed (h−1) | Medium speed (h−1) | High speed (h−1) | Analysis period (h) |
---|---|---|---|---|---|
0 | 0.35–0.46 | 0.44 | 0.37 | 0.55 | 2.0 |
1 | 0.46–0.66 | 0.68 | 0.60 | 0.76 | 2.0 |
2 | 0.66–1.0 | 0.79 | 0.72 | 0.89 | 2.0 |
3 | 1.0–1.3 | 0.91 | 0.86 | 1.06 | 2.0 |
4 | 1.3–1.7 | 1.02 | 0.97 | 1.17 | 2.0 |
5 | 1.7–2.3 | 1.17 | 1.17 | 1.35 | 2.0 |
6 | 2.3–3.0 | 1.38 | 1.58 | 1.69 | 0.6–0.9 |
A modified CADRfilter, meaning the CADR attributed to the filters only, was calculated from eqn (3):
CADRfilter(j) = (ACHf+d+i(j) − ACHd+i+fan(j))V | (3) |
Q(j) = (CADRfilter(j)/SPFE(j)) | (4) |
The CADRfilter values were used here instead of the CADR values so as to focus on just the airflow through the filters. The calculated flow rate for a CR box should be the same across all particle size bins. Any size-dependent differences in the flow result are attributed to the uncertainty in the measurements of CADRfilter and SPFE. The average flow rate () was calculated as the average across all seven size bins. The 95% confidence interval was calculated as two standard deviations across the seven measurements.
The mass deposited on the filters over each deployment period was estimated per eqn (4). For each fan speed i, the cumulative mass deposited was estimated by multiplying the number of hours (t) of operation (as measured by the power meter), the average particle mass concentration as measured by Purple Air and the average CADR for all particle bins The total estimated mass was calculated as the sum of the mass collected at each fan speed (low, medium, high). These data were used to estimate the cumulative mass deposited on the box at the time each set of CADR and SPFE measurements were taken.
(5) |
Box | Main speed | Initial power (W) | Final power (W) | % change |
---|---|---|---|---|
1 | Medium | 72.6 | 73.3 | 1.0% |
2 | Low | 63.2 | 60.3 | −4.5% |
3 | High | 86.5 | 87.1 | 0.7% |
4 | Low | 60.1 | 60.3 | 0.4% |
Fig. 2 CADR results for CR boxes as a function of cumulative mass deposited over the 40 week field trial. Coefficients for the linear and quadratic fits are provided in Tables S2 and S3.† Error bars represent an estimated uncertainty of 6% for 0.35 to 1 μm optical diameter particles and 5% for 1 to 3 optical diameter particles. |
Overall the CADR measurements (and associated cost-effectiveness) for new CR boxes (514 to 1387 m3 h−1, depending on box, fan speed, and particle size) were within range of others reported in the literature (Fig. 2).18 Box 1 (AH filters) outperformed the other CR boxes, both when new and throughout the study. This illustrates that filter selection, even among those rated MERV 13, may impact performance. In addition to differences in box fans, filter selection likely contributes to the wide range of CADR results reported in the literature.18 In addition to actual differences in CR box performance due to material selection, measurement methods will influence results because of CADR dependence on particle size. For example, use of sensors and methods that calculate CADR based on particle mass removal rates (as opposed to particle count removal rates) are likely to yield higher CADR results because MERV 13 filters have higher removal rates of larger particles that dominate mass-based measurements.
This study was designed to assess the long-term performance of CR boxes and was not designed to assess differences between MERV 13 filter brands, and we did not expect the results to be different for the box built with a different brand of filter. The minimum 0.3 to 1.0 μm diameter particle removal efficiency must be at least 50% for MERV 13 filters and 75% for MERV 14 filters. The large jump in filtration efficiency between MERV 13 and MERV 14 shows that there could be variation among MERV 13 filters brands that meet or exceed the MERV 13 standard but are still classified as such.27 Both types of filters used in this study met requirements of MERV 13 filters, with a small difference between the filters' initial filtration efficiency (e.g. AH 61% and TA 55% for 0.3 to 1.0 μm particles) per the ASHRAE 52.2-2017 test reports, which were obtained from the manufacturers.28,29 Although initial filtration efficiency differences were small, CR box builders may benefit from reviewing manufacturer provided filtration performance data when making filter selection instead of only considering MERV rating (in addition to consideration of filter cost).
As expected for MERV 13 filters, the CADR for 1.0–3.0 μm optical diameter particles was consistently higher than the CADR for 0.35–1.0 μm optical diameter particles because they are more easily removed by impaction with filter fibres.30 Across four CR boxes tested at three speeds at five times during the 40 week deployment (n = 60), the CADR for 1.0–3.0 μm optical diameter particles was, on average, 34% higher than the CADR for 0.35–1.0 μm optical diameter particles.
The CADR for CR boxes 2, 3, and 4 (TA filters) declined approximately linearly with particle accumulation on the filters (Fig. 2). Considering these three CR boxes as one dataset, a linear least-squares regression estimated that, after 4.8 g of particles was deposited, the CADR was 62–63% of the new CR box performance for particles 0.35 to 1.0 μm optical diameter and 69–70% of the new CR box performance for particles 1.0 to 3.0 μm optical diameter.
The CADR for CR box 1 was higher than CR boxes 2, 3, and 4. A two-sample t-test comparing all CADR measurements for box 1 to all CADR measurements for box 2, 3, and 4 (at the same speed) determined that the higher value of CADR for box 1 was statistically significant at high speed (p = 6.6 × 10−7) and medium speed (p = 1.5 × 10−3) but not at low speed (p = 0.20). Coincidentally, box 1 was deployed in the dustiest environment and accumulated an estimated 9.6 g of particles on the filters over the course of the deployment. Box 1 appeared to have an increase in CADR in almost all cases between the first and second measurements (except high speed, 0.35 to 1.0 μm optical diameter particles). CADR generally decreased in subsequent measurements. A quadratic least-squares regression estimated that, after 9.6 g of particles was deposited, the CADR was 63–75% of the new CR box performance for particles 0.35 to 1.0 μm optical diameter and 70–84% of the new CR box performance for particles 1.0 to 3.0 μm optical diameter. CADR was better maintained at high and medium speed than low speed. The sample size of one box with AH filters is too limited to draw general conclusions; it is unknown if a larger sample size would exhibit similar behaviour.
Analysis of the CADR results alone cannot determine if the CADR is decreasing due to a loss of filtration efficiency or due to a reduction in flow rate due to increased resistance of the filters. The SPFE measurements, flow rate calculations, and power measurements provide insight to the reasons for the performance decrease.
CR box | Deployment period | Hours of operation | Speed | (m3 h−1) | Average PM10 (μg m−3) | PM10 10th percentile (μg m−3) | PM10 90th percentile (μg m−3) | % PM10 data available | Estimated PM10 deposited (g) | Estimated cumulative PM10 deposited (g) |
---|---|---|---|---|---|---|---|---|---|---|
1 | 1 | 639 | Medium | 978 | 7.05 | 2.21 | 13.24 | 45% | 4.41 | 4.41 |
2 | 63 | Medium | 969 | 2.15 | 0.06 | 2.55 | 100% | 0.13 | 4.54 | |
585 | Low | 677 | 5.41 | 0.47 | 11.48 | 73% | 2.14 | 6.68 | ||
3 | 369 | Medium | 825 | 5.14 | 0.06 | 13.81 | 100% | 1.57 | 8.25 | |
261 | Low | 555 | 4.94 | 0.20 | 11.55 | 100% | 0.72 | 8.96 | ||
4 | 432 | Medium | 768 | 2.00 | 0.05 | 7.26 | 25% | 0.66 | 9.63 | |
Total box 1 | 2349 | 9.6 | ||||||||
2 | 1 | 639 | Low | 591 | 6.14 | 1.08 | 12.13 | 100% | 2.43 | 2.32 |
2 | 648 | Low | 507 | 5.14 | 0.31 | 10.56 | 100% | 1.69 | 4.00 | |
3 | 630 | Low | 456 | 1.98 | 0.04 | 5.66 | 100% | 0.57 | 4.57 | |
4 | 693 | Low* | 435 | 0.83 | 0.03 | 1.80 | 100% | 0.25 | 4.82 | |
Total box 2 | 2610 | 4.8 | ||||||||
3 | 1 | 297 | Medium | 820 | 0.92 | 0.05 | 2.19 | 100% | 0.22 | 0.22 |
1 | 342 | High | 1027 | 1.02 | 0.03 | 1.96 | 92% | 0.45 | 0.58 | |
2 | 648 | High | 904 | 0.54 | 0.00 | 1.48 | 100% | 0.32 | 0.90 | |
3 | 459 | High | 842 | 0.45 | 0.00 | 1.24 | 100% | 0.17 | 1.07 | |
171 | Medium | 654 | 0.35 | 0.00 | 1.14 | 100% | 0.04 | 1.11 | ||
4 | 135 | Medium | 683 | 0.18 | 0.00 | 0.44 | 100% | 0.02 | 1.13 | |
558 | High | 808 | 0.07 | 0.00 | 0.19 | 100% | 0.03 | 1.16 | ||
Total box 3 | 2610 | 1.2 | ||||||||
4 | 1 | 639 | Low | 644 | 2.01 | 0.11 | 4.54 | 100% | 0.94 | 0.83 |
2 | 648 | Low | 585 | 1.52 | 0.05 | 3.66 | 100% | 0.57 | 1.40 | |
3 | 576 | Low | 550 | 1.09 | 0.01 | 3.28 | 100% | 0.34 | 1.75 | |
4 | 693 | Low | 557 | 0.30 | 0.01 | 0.91 | 100% | 0.12 | 1.87 | |
Total box 4 | 2556 | 1.9 |
Fig. 4 SPFE results for CR boxes as a function of cumulative mass deposited at 0, 30, and 40 weeks. Error bars represent an estimate 20% relative error on the SPFE measurement. |
The SPFE for CR box 1 was consistently higher than CR boxes 2, 3, and 4. The SPFE declined over time for all boxes. A contradiction in the data is an apparent increase in CADR for box 1 between the first and second measurements along with an initial SPFE of nearly 1 (SPFE was not measured at the second test period). An increase in CADR would occur from either an increase in filtration efficiency or an increase in airflow through the filter. There is no physical rationale for an increase in airflow over time, as the fan motor was unchanged, and filter resistance increased with time (see sections on power and total airflow rate and pressure drop). Likewise, if SPFE started at the maximum of 1 as observed, it would be impossible to increase. Therefore, the remaining explanations for the results observed are error in the SPFE measurement (such that the measured value is higher than actual) or error in the CADR measurement (such that the difference between the first and second measurement is not significant). Larger sample sizes would be needed to investigate this further. While we applied a quadratic fit to the box 1 results to help visualize the observation, we do not intend to imply the observed increase in CADR is statistically significant.
Collectively for CR boxes 2, 3, and 4, the decline in SPFE was correlated with the cumulative mass deposited. This likely results from the filters having an initial electrostatic effect that is reduced as the filter accumulates particles.31 Both manufacturers confirmed that the filters use both charged fibres and mechanical principles to remove particles. ASHRAE 52.2 testing that is used to determine MERV rating does not take into account electrostatic discharge. The difference in the SPFE between the CR boxes indicates that box 1 filters may rely less on initial electrostatic forces to meet their stated initial MERV performance (since the box 1 removal efficiency better persists with particle accumulation). Unfortunately, performance data after electrostatic discharge are not generally available to the consumer in ASHRAE 52.2 test reports (unless optional appendix J is used).
Complete pressure drop measurements are available in the ESI, Table S13.† At high speed, the static pressure drop across new boxes was 7.1 to 7.2 Pa and the final pressure drop was 8.2 to 10.9 Pa, where the highest final pressure drop was observed for box 1. This increase in pressure is small relative to the total external static pressure across the fan. For example, an increase of static pressure of 3 Pa at a flow rate of 1500 m3 h−1 is equal to a fluid power loss of only 1.3 W. Although the efficiency of the fan and motor assembly is not known (so conversion to electrical power cannot be estimated), 1.3 W is small compared to the electrical input of the box fan at high speed (86 W). Therefore, while particle accumulation on the filters will increase resistance, the change is small relative to the external static pressure across the fan system and thus is expected to have minimal impact on total flow rate.
A second limitation was the estimate of PM10 cumulative mass. This metric was used to provide more information than the cumulative runtime because particle concentrations in the indoor environment vary widely. As discussed in the methodology, low-cost Purple Air sensors have only moderate correlation with PM10 reference measurements. An improvement to this study methodology would be to deploy periodic PM10 reference instruments (e.g. 1 week per deployment period) to calibrate the Purple Air sensors for the specific environments in which they are deployed.
Finally, in this study we did not directly measure airflow through the CR box. Methods that measure air velocity are challenging because they require many individual measurements and assumptions on the applicable area for the measured velocity to calculate flow.3 As such, we estimated airflow as the ratio of measured CADR and SPFE. A limitation of this approach is a high uncertainty of the SPFE measurement, which impacts uncertainty of the total flow calculation.
Considering all three boxes with the same filter brand (TA) as one dataset, a linear least-squares regression estimated that, after 4.8 g of particles were deposited, the CADR was 62–63% of its initial value for particles 0.35 to 1.0 μm optical diameter and 69–70% of its initial value for particles 1.0 to 3.0 μm optical diameter. For the CR box with a different filter brand (AH), a quadratic least squares regression estimated that, after 9.6 g of particles deposited, the CADR was 63–75% of its initial value for particles of 0.35 to 1.0 μm optical diameter and 70–84% of its initial value for particles 1.0 to 3.0 μm optical diameter. Since CR boxes are an order of magnitude less in cost than HEPA filters and they maintain at least 60% of their initial CADR (even after 40 weeks of daily operation in dirty lab environments), they are a cost-effective long-term tool to manage air quality. The results indicate that annual filter replacements are sufficient in dirty environments and that filters may last 2–3 years in clean office environments. No substantial wildfire smoke was observed during the study period. A study by Liang et al. quantified that indoor air PM2.5 was approximately 2.7 times higher on “fire days” versus “non-fire days”.32 Thus, the occasional and short-term presence of wildfire smoke is not expected to appreciably affect the 1–3 year lifetime of the CR box.
Performance losses as particles accumulated were attributed to loss of single pass filtration efficiency (likely due to loss of initial electrostatic charge on the filters). Although total airflow rate measurements had high uncertainty, there were no indications that minimally increased filtration resistance significantly affected airflow, even for CR boxes operating in laboratory environments with sources of particle generation.
Footnote |