Sarath
Kumara‡
a,
Amir Masoud
Pourrahimi‡
b,
Azadeh
Soroudi‡
b,
Xiangdong
Xu
*a,
Thomas
Hammarström
a,
Yuriy
Serdyuk
a and
Christian
Müller
*b
aDepartment of Electrical Engineering, Chalmers University of Technology, Gothenburg 41296, Sweden. E-mail: christian.muller@chalmers.se; xiangdong.xu@chalmers.se
bDepartment of Chemistry and Chemical Engineering, Chalmers University of Technology, Gothenburg 41296, Sweden
First published on 10th May 2022
Click chemistry type reactions between polyethylene-based copolymers are a promising and by-product free alternative to peroxide crosslinking of low-density polyethylene, which is widely used as an insulation material for high-voltage power cables. Here, the impact of thermal ageing on the long-term stability of the thermo-mechanical and dielectric properties of a copolymer blend is evaluated that can be cured through a by-product free reaction between the epoxy and carboxylic acid functional groups attached to the polyethylene backbone. It is observed that ageing at 90 °C in air for up to 2500 h does not affect the direct current (DC) electrical conductivity of about 3 × 10−14 S m−1, provided that a suitable antioxidant is added that prevents the thermo-oxidative degradation of the polyethylene backbone. Furthermore, the material maintains its thermo-mechanical properties upon ageing such as a high ductility at room temperature and a stiffness of about 1 MPa above the melting temperature of polyethylene. Evidently, the use of click chemistry type reactions is a promising strategy for the design of new high-voltage insulation materials that can be cured without the formation of by-products.
Crosslinked low-density polyethylene (XLPE) is the most widely used insulating material for extruded HVDC cables. XLPE based insulating materials feature a low direct current (DC) electrical conductivity of σDC ≈ 2 × 10−14 S m−1 at 70 °C – a typical cable operating temperature – and an electric field exposure of up to 20 kV mm−1.5,6 The insulating properties can be improved further by adding conductivity reducing additives, such as metal oxide nanoparticles,7–9 conjugated polymers10 and aromatic voltage stabilisers,11–13 as well as a small amount of high-density polyethylene.14
XLPE based insulation materials are obtained by radical crosslinking of low-density polyethylene (LDPE) using peroxides such as dicumyl peroxide (DCP). The peroxide curing process results in by-products such as methane, acetophenone, cumyl alcohol, and α-methylstyrene,15,16 which can increase the DC electrical conductivity and pose a potential health and safety hazard. Hence, by-products need to be removed, which is typically performed using a time and energy consuming degassing procedure.17 As a result, strategies that reduce or avoid the generation of by-products during the crosslinking process are of great importance. One approach is to reduce the amount of peroxides that are needed for radical crosslinking, which can be achieved through the incorporation of vinyl groups.18 Another strategy involves the development of insulation materials that can be cured through a click chemistry-type crosslinking reaction, which does not produce any by-products.5,19–21
Click chemistry-type crosslinking can be realised by using blends of polyethylene copolymers that comprise functional groups, which can undergo a curing reaction. We have previously studied blends of a statistical ethylene–glycidyl methacrylate copolymer, p(E-stat-GMA) and a statistical ethylene–acrylic acid copolymer, p(E-stat-AA) (see Fig. 1 for chemical structures).5,19 These two types of copolymers can be compounded at, e.g., 120 °C, which lies above their respective melting temperatures of Tm ≈ 108 °C and 101 °C. Heating to temperatures above 140 °C triggers the curing reaction that leads to the formation of a covalent crosslink (Fig. 1).5 The cured blends display a DC electrical conductivity of about 1 × 10−14 S m−1 measured at 70 °C and 20 kV mm−1 provided that the overall comonomer content is sufficiently low.5,6 It is of paramount importance that the excellent dielectric properties of click chemistry-cured copolymer blends do not deteriorate with time. Ageing of polyethylene-based insulation materials can introduce chemical defects as well as structural changes, which can negatively affect their dielectric and thermo-mechanical properties22–26 and hence may cause electrical treeing as well as a decrease in the dielectric breakdown strength.27–30
Here, we study how long-term ageing at 90 °C – the currently highest HVDC cable operating temperature – for up to 2500 h influences the dielectric and thermo-mechanical properties of a cured copolymer blend comprising p(E-stat-GMA) and p(E-stat-AA). We found that the electrical conductivity is not affected by ageing provided that a suitable antioxidant is added.
In a first set of experiments, we recorded differential scanning calorimetry (DSC) isotherms at 190 °C in air to determine the extent of thermo-oxidative degradation. For the cured blend, we observe the onset of an exothermic degradation process as soon as air is introduced (Fig. 2). The deviation from the isothermal baseline after the gas switch suggests the immediate degradation of the cured blend that does not contain the antioxidant with an oxidation induction time (OIT) of 0 min. In most significant contrast, the isotherm recorded for the cured blend containing 0.1 wt% Irganox features a significantly reduced exotherm at t > 5 min which suggests that the OIT exceeds the duration of the experiment (OIT > 30 min), indicating that the antioxidant can largely suppress thermo-oxidative degradation.
Fig. 2 DSC isotherm at 190 °C under an air flow (t > 5 min) for the cured binary blend without the antioxidant (red) and the cured binary blend with 0.1 wt% Irganox (blue). |
The cured blend samples were aged at 90 °C for 500 to 2500 h at ambient atmosphere, and Fourier-transform infrared (FTIR) spectroscopy was performed to investigate the chemical processes that underlie the observed thermo-oxidative degradation of the cured blend without the antioxidant. The as-cured blend features two absorption peaks at 1705 cm−1 and 1735 cm−1 prior to ageing (Fig. 3a), which we assign to the stretching vibrations of carbonyl groups that are part of (1) carboxylic acid dimers and (2) the ester of GMA or the covalent crosslink, respectively (see Fig. 1).19 The cured blend containing Irganox features a more pronounced absorption at 1735 cm−1 relative to the absorption at 1705 cm−1, when compared to the cured blend without the antioxidant. The more extensive consumption of carboxylic acid groups is consistent with a higher degree of crosslinking as discussed below.
In the case of blends without the antioxidant, a distinct new absorption peak emerges at 1714 cm−1 upon ageing, which we assign to the stretching vibrations of carbonyl groups that are introduced to the polyethylene backbone in the form of ketones as a result of thermo-oxidative degradation (Fig. 3a).31–33 Instead, ageing did not significantly affect the FTIR spectra of the cured blend with the antioxidant (Fig. 3a), indicating that the presence of 0.1 wt% Irganox is able to suppress the oxidation of the cured blend. We used the absorption at 1714 cm−1 to monitor the thermo-oxidative degradation at 90 °C (Fig. 3b). The samples without the antioxidant underwent rapid thermo-oxidative degradation already during the first 500 hours of ageing while the samples with the antioxidant featured an invariant FTIR absorption in the carbonyl region up to 2500 h of ageing at 90 °C. The OIT of samples containing 0.1 wt% Irganox and aged for up to 2000 h was longer than 30 min (the same as samples prior to ageing, see Fig. 2), while, for an ageing time of 2500 h, an OIT of about 5 min was obtained (Fig. S1, ESI†). This observation indicates that the material contained a sufficient amount of antioxidant to hinder thermo-oxidation for at least 2500 h of ageing at 90 °C. It is expected that a higher content of Irganox 1010 would increase the OIT of the material aged for 2500 h.
Dynamic mechanical analysis (DMA) was used to investigate how ageing influences the storage modulus E′ of the materials. The DMA thermograms of the samples aged for 1000 h are characteristic for the cured blends (Fig. 4a). Both materials display a considerable decrease in stiffness above the melting temperatures of the two copolymers, p(E-stat-GMA) and p(E-stat-AA), i.e. Tm ≈ 108 °C and 101 °C.5 The cured binary blend features a rubber plateau above the melting temperature with a value of Ep ≈ 0.2 MPa in the case of the cured blend without the antioxidant, while the Irganox-containing blend shows a higher value of Ep ≈ 1 MPa after 1000 h of ageing. The rubber plateau modulus can be used to estimate the molecular weight between network points (network points can be crosslinks, trapped entanglements, etc.) according to Mc = ρRT/Ep, where ρ = 0.789 cm−3 is the density of polyethylene at T = 140 °C. We obtain values of 13.5 kg mol−1 and 2.7 kg mol−1 for the cured blend without and with Irganox (consistent with the FTIR spectra of the cured blends; see Fig. 3a), which corresponds to 1 and 5 network points per 1000 carbons, respectively, i.e. comparable to a previously obtained value of 3.5 network points per 1000 carbons for the same curing time and temperature.5 The two copolymers p(E-stat-AA) and p(E-stat-GMA) have a comonomer-to-ethylene ratio of 1:108 GMA:E and 1:83 AA:E, respectively, which implies that the complete consumption of all functional groups would give rise to about 5 crosslinks per 1000 carbons. We have previously shown that the cured blends of p(E-stat-AA) and p(E-stat-GMA) contain not only covalent crosslinks but also a significant fraction of physical network points in the form of (trapped) entanglements.19
Fig. 4 (a) DMA thermograms of the samples aged for 1000 h and (b) storage modulus versus ageing time at 30 °C and 150 °C of the cured binary blend without (red) and with 0.1 wt% Irganox (blue). |
To explore whether ageing alters the stiffness of the materials, the storage moduli at 30 °C and 150 °C were plotted versus the ageing time. The storage modulus below the melting temperature was unaffected by ageing (Fig. 4b). This observation is consistent with an invariant crystallinity of about 30%, as determined by DSC (ESI† Fig. S2). The rubber plateau modulus of the cured blend, with and without antioxidant, first decreased upon ageing for 500 h but then gradually increased upon ageing for longer times. We argue that ageing at 90 °C, which is close to the melting temperature of the copolymers, facilitates the reorganisation of at least some physical network points, leading to a slight decrease in the rubber plateau. More long-term ageing, however, leads to a gradual increase in the rubber plateau because the curing reaction slowly proceeds at the chosen annealing temperature.
To investigate the impact of ageing at 90 °C on the dielectric properties of the cured blends, leakage currents were recorded at 70 °C and 20 kV mm−1. The leakage current of the cured blends that did not contain the antioxidant significantly increased by more than two orders of magnitude as a result of ageing, while the cured blends with Irganox displayed an invariant leakage current (Fig. 5a). The DC electrical conductivity was calculated based on the leakage current measured after 12 h. The cured blend without the antioxidant features a low σDC of 2 × 10−14 S m−1 at 70 °C and 20 kV mm−1 (Fig. 5b; see ESI† Fig. S3 for measurements at 30 °C and 50 °C), which is comparable to the σDC of LDPE measured under the same conditions.5 The cured blend with Irganox only had a slightly higher value of σDC ≈ 3 × 10−14 S m−1, which we assign to the presence of the antioxidant.34 The DC electrical conductivity of the cured blend without the antioxidant strongly increased with ageing time, reaching a value of σDC ≈ 2 × 10−11 S m−1 after 1000 h at 90 °C. In contrast, the cured blend containing Irganox displayed the same DC electrical conductivity up to at least 2500 h of ageing at 90 °C.
In a final set of experiments, frequency domain spectroscopy (FDS) was carried out to study the frequency dependence of the dielectric response from 0.1 mHz to 1 kHz from which the loss tangent was determined (Fig. S4, ESI†). We found that for the cured blend without antioxidant the loss tangent at 50 Hz increases with ageing time, e.g. from about 5 × 10−4 to 3 × 10−3 at 70 °C after 2500 h of ageing at 90 °C (Fig. S5, ESI†). Instead, the loss tangent recorded for the binary blend with the antioxidant only slightly changed upon ageing, e.g. from about 4 × 10−4 to 6 × 10−4 under the same conditions. Evidently, the presence of 0.1 wt% Irganox can prevent the degradation of the dielectric properties up to at least 2500 h.